APPLICATIONS
To suppress harmonics in the neutral
POWER / ATRYS ratings:
15 kVA / 15 A
30 kVA / 27 A
60 kVA / 54 A
90 kVA / 82 A
200 kVA / 180 A
280 kVA / 240 A
ADVANTAGES
Suppresses the main harmonics
generated by PCs, servers, printers, discharge lamps…
Neutralises harmonics as close as possible to the polluting equipment.
Eliminates the problems associated with harmonic 3 in the neutral overload, ageing, downgrading of installations, spurious tripping of protective devices.
Increases the lifetime of installations
Improves the installation´s power factor
Reduces the current consumed
Reduces energy costs
Meets the needs of all types of electrical networks including those supplied from gen sets fitted with power factor correction capacitors or filters.
Easy to install and operate
The addition of a DIRIS Mh measuring device will provide operational information about current and voltage harmonics, current and voltage distorsion, current values (phase and neutral), voltage and frequency.
DIMENSIONS
power (kVA) | ATRYS rating (A) | width (mm) | depth (mm) | height (mm) | weight (kg) |
15 | 15 | 550 | 400 | 750 | 100 |
30 | 24 | 550 | 400 | 750 | 110 |
60 | 57 | 640 | 400 | 750 | 210 |
90 | 82 | 800 | 450 | 1400 | 320 |
200 | 180 | 800 | 610 | 1925 | 740 |
280 | 240 | 800 | 610 | 1925 | 760 |
TECHNICAL DATA
ATRYS rating | 15 A | 27 A | 54 A | 82 A | 180 A | 240 A |
Application power | 15 kVA | 30 kVA | 60 kVA | 90 kVA | 200 kVA | 280 kVA |
Phase current | 23 A | 45 A | 87 A | 130 A | 290 A | 406 A |
Max. neutral current | 45 A | 81 A | 162 A | 245 A | 540 A | 720 A |
Elimination of phase harmonics(phases H3, H9, H15) | up to 80 % | |||||
Elimination of neutral harmonics | up to 85 % | |||||
Rated voltage | 400 V 3 phases + N (+/- 15 %) | |||||
Rated frequency | 50 Hz (+/- 6 %) and 60 Hz | |||||
Standard | In accordance with 60439-1 | |||||
Color | RAL 9001 | |||||
Protection level | (IP 32 optional) | |||||
Operating temperature | up to 40 °C |