| Line | H |
| Code generator with automatic | FG HIS 50 AH |
| Code generator with manual control | FG HIS 50 MH |
| Aggregate: | |
| Maximum power LTP [kVA] | 55.0 |
| LTP Maximum Power [kW] | 44.0 |
| PRP Rated power [kVA] | 50.0 |
| PRP Rated power [kW] | 40.0 |
| Rated current [A] | 72.2 |
| Frequency [Hz] | 50 |
| Voltage [V] | 400 |
| Generator: | |
| The manufacturer of the generator | Sincro |
| Country of production | Croatia |
| Type of generator | IB 4 LA |
| Power generator (40 ° C, 1000m above sea level) [kVA] | 50.0 |
| Generator efficiency [%] | 90.7 |
| Voltage stabilization | AVR Analog |
| The level of voltage stabilization [%] | +/- 1 |
| Protection [IP] | 23 |
| Insulation class | H |
| Current harmonic distortion THD [%] | <2.5 |
| Reactance X”d [%] | 12.0 |
| Engine: | |
| Engine Manufacturer | Iveco |
| Country of production | Italy |
| Engine Type | F32TM1 |
| Net engine power [kW] | 47.0 |
| Turnover [r / min] | 1500 |
| Speed control | Mechanical |
| The classification of | G2 |
| Engine capacity [l] | 3.2 |
| Number of cylinders | 4 |
| Installation of [V] | 12 |
| Cooling | fluid Shell Anti Freeze |
| The capacity of the cooling system [l] | 19.5 |
| Engine Oil | Shell Rimula R4L |
| Oil capacity [l] | 10.5 |
| Exhaust Emissions | Stage II |
| Type of fuel | Diesel (EN 590) |
| Fuel consumption for the load of 80% [l / h] | 10.2 |
| The fuel consumption for 100% load [l / h] | 12.6 |
| Aggregate: | |
| Fuel tank capacity [l] | 125 |
| Working time for a load of 100% [h] | 9.9 |
| The weight of the unit without the fuel [kg] | 850 |
| Dimensions L x W x H [mm] | 1850 x 880 x 1294 |
| Lion Guaranteed sound power level [dB] | 110.9 ± 0.7 |