UPS DELPHYS BC (160 to 300 kVA)

The solution for

• Data servers
• Data centres

Advantages

A COMPLETE, COST-EFFECTIVE SOLUTION

• Online double conversion mode with an output power factor of 0.9 providing 12% more active power compare to UPS with a power factor of 0.8.
• Dual input mains allows you to manage independent power sources.
• Increased system availability placing two UPS in parallel for 1+1 redundancy
• Internal manual bypass for easy maintenance without power interruption.
• Multilanguage display.

TAILORED TO YOUR ENVIRONMENT

• Saves space with a reduced footprint and optimized cabinet size.
• Low noise level.
• Compact, lightweight and easy to install
• Extended battery life and performance with exclusive EBS battery charging management for increased battery life.

STANDARD ELECTRICAL FEATURES

• Dual input mains.
• Internal maintanance bypass.
• Backfeed protection: detection circuit.
• EBS (Expert Battery System) for battery management.

ELECTRICAL OPTIONS

• External battery cabinet.
• External temperature sensor.
• Additional battery chargers.
• Shared battery.
• Galvanic isolation transformer.
• Parallel kit.
• ACS synchronization system.

STANDARD COMMUNICATION FEATURES

• 2 slots for communication options.

COMMUNICATION OPTIONS

• Dry-contact interface.
• MODBUS TCP.
• MODBUS/JBUS RTU
• PROFIBUS
• NET VISION: professional WEB/SNM interface for UPS monitoring and shutdown management of several operating systems.

REMOTE MONITORING SERVICE

• LINK-UPS, remote monitoring service that connects your UPS to your Critical Power specialist 24 / 7.

Technical data

 

Sn [kVA] 160 200 300
Pn [kW] 144 180 270
Parallel configuration 1+1(1)
Input
Rated voltage 400 V 3ph
Voltage tolerances 240 V to 480 V(2)
Rated frequency  50/60 Hz ± 10%
Power factor / THDI 0.99 / < 3%
Output
Rated voltage 400 V
Voltage tolerance  static load ±1% dynamic load in accordance with VFI-SS-111
Rated frequency 50 / 60 Hz
Frequency tolerance ± 2% (configurable from 1% to 8%)
Crest factor 3:1
Bypass
Rated voltage rated output voltage
Voltage tolerance ± 15% (configurable with from 10% to 20%)
Rated frequency 50/60 Hz
Frequency tolerance ± 2% (configurable for Genset compatibility)
Efficiency
Online mode @ 100 % of load up to 94%
Environment
Operating ambient temperature from 0 °C up to + 40(2) °C
(from 15 °C to 25 °C for maximum battery life)
Relative humidity 0% – 95% without condensation
Maximum altitude 1000 m without derating (max. 3000 m)
Acoustic level at 1 m
(ISO 3746)
< 68 dBA < 71 dBA
UPS cabinet
Dimensions W x D x H 700 x 800 x 1930 mm 1000 x 950 x 1930 mm
Weight (2) 480 kg 500 kg 830 kg
Degree of protection IP20
Colours RAL 7012, silver grey frontal door
Standards
Safety EN 62040-1 (TÜV SÜD certified), EN 60950-1
Performance EN62040-3 (VFI-SS-111)
EMC EN62040-2
Product declaration CE

(1) The standard model is prepared for a 1+1 redundant system. Upon request, it is possible to have connected up to 6 modules in a parallel system.
(2) Conditions apply.