Flywheel technology VSS+ DC (Voltage Support Solution)

APPLICATIONS

Backs up the DELPHYS UPS, overcoming the constraints, risks, costs and hazards of batteries. The solution inverter DELPHYS with dynamic storage of energy VSS+ DC was carried out by SOCOMEC UPS.
PRINCIPLE

VSS+ DC uses a very high-speed, rotating flywheel.The rotating assembly is held up by maintenance-free electromagnetic levitation, with no contact with other parts. A maintenance-free internal system vacuum eliminates friction and maximizes energy efficiency. The flywheel-driven generator supplies energy to the UPS during a power failure, thus providing continuous power to the load. When mains power is restored, the flywheel takes less than 5 minutes to return to full speed.

465FD4SS6

1. Containment housing
2. Composite carbon-fiber flywheel
3. Stator windings
4. Upper magnetic bearing
5. Vacuum system
6. Rotor
7. Lower magnetic bearing

ADVANTAGES

• Outstanding reliability : long service life (20 years)
• Extremely infrequent maintenance
• No vacuum pump maintenance
• Max. power in min. volume
• High efficiency > 99.8%
• Rapid recharging (5 minutes as standard)
• Virtually silent operation
• No load restrictions on ground
• Installation requiring no structural work
• Environmentally-friendly

THE VARIOUS CONFIGURATIONS Various solutions or combinations for meeting your requirements for electrical energy availability are possible depending on your operating constraints and technical environment.

1. short-duration POWER OUTAGES The VSS+ DC system is connected to the DC bus; it supplies the inverter when the low-voltage system exceeds the voltage tolerances. Thereby providing 99.5% protection against system failures.

2. working with a generator unit The VSS + DC supplies the inverter long enough for an emergency generator to take over the power supply and rapidly recharge the VSS + DC.

3. working with a battery When connected in parallel with a battery bank, the VSS+ DC cuts in during all short power failures and voltage sags; battery backup is used only for long duration cuts (or not at all if a backup generator is present). Battery life is extended by very infrequent demands.

4. working in parallel VSS+ DC units connected in parallel increase power and available backup time. No communications hardware or software needed, this capability is built-in.

65F4D

 

DIMENSIONS

width height depth weight
 630 mm  1800 mm 830 mm 590 kg

 

TECHNICAL

Electrical  
Nominal full power duration with DELPHYS MP Elite 200 kVA/160 kW: 17 sec*.
160 kVA/128 kW: 21 sec*.
120 kVA/96 kW: 27 sec.
100 kVA/80 kW: 33 sec.
80 kVA/64 kW: 40 sec.
60 kVA/48 kW: 50 sec.
Voltage (input/output) 420*-570 V DC
Output voltage control ± 1% under static conditions
Ripple factor < 2 %
Auxiliary voltage 110/230 V AC
Auxiliary power 400 VA
Environment  
Sound level (ISO3746) < 45 dB
Operating temperature - 20 °C to + 50 °C
Operating altitude up to 3000 metres
Conformity with standards CEE 73/23 Low voltage directive

CEE 98/037 Machine directive
IEC/EC 60439-1
IEC/EN 60204-1 Machine safety
EN1127-1 Explosive atmospheres

* On 160 and 200 kVA versions, the power available depends on the DC voltage of the BUS to the UP