UPS MODULYS TC (3000-9000 VA)

from 3 to 9 kVA Telecom applications and long back up times

Categories: ,

from 3 to 9 kVA
Telecom applications and long back up times

With its special architecture, specifically designed for the telecommunications sector, and the long back-up time guaranteed by its standard “Long Life” batteries, the Mod-TC 245 is also the ideal solution for installations in remote unmanned places such as radio links, radio mobile stations for cellular phone networks, and GSM – GPRS – UMTS – repeaters.

THE TWO VERSIONS PROVIDED:

MOD-TC 230 (1 X 3000VA) / MOD-TC 245 (1 X 4500VA) / MOD-TC 260 (1 X 6000VA)
MODULYS TC2xx is a Stand Alone UPS, with power ratings of 3000VA (TC230), 4500VA (TC245) or 6000VA (TC260) with the option of installing a second completely independent UPS of the same power.

MOD-TC360 (2 X 3000VA) / MOD-TC390 (2 X 4500VA)
MODULYS TC3xx is a scalable and modular UPS, which can be expanded in both power and redundancy. Because of its modular nature, the 6000VA system (TC360) can in fact be increased to 9000VA, or offer a 6000VA N+1 redundant system. In the same way, with the installation of a third 4500VA module, the 9000VA system (TC390) can operate as a 9000VA N+1 redundant system.
Furthermore, in order to guarantee continuous and reliable operation, the specific battery charger installed as standard enables the fast and stable recharging of the batteries after any use in autonomous operation.
The VFI (Voltage Frequency Independent) architecture means that the Mod-TC can also be used as a frequency converter, making it particularly suitable for the power of all equipment requiring different power supply frequency. This UPS can in fact receive 50 Hz frequency input and supply 60 Hz in output, and vice versa.
Also available is the ECO-MODE function which amplifies these features and offers considerable energy savings, ideal during periods when the priority loads are off. This function can be programmed by the user and means that the level of protection offered by the UPS when the mains line is down remains unaltered.

ADVANTAGES
FLEXIBLE: THE UPS THAT GROWS WITH YOUR COMPANY

MODULYS offers total adaptability, fitting to existing architecture and installations, facilitating their evolution, and even making it possible to migrate from a tower to a rack configuration.
Specifically designed for optimal modularity, MODULYS can be adapted to fit all dimensions and to meet all requirements.

ECONOMICAL: THE SYSTEM MODULARITY SAFEGUARDS YOUR INITIAL INVESTMENT
No matter what the nature of your evolution is (power, autonomy), each unit of your MODULYS system can be re-used to recompose your new power supply protection.

SIMPLE: THE SIMPLEST UPS THAT HAS IT ALL
Easy to install and use, MODULYS is a functional UPS design. All the power and autonomy units are “plug in”, meaning they can be connected without interrupting your power supply.

RELIABLE: THE UPS THAT IS AHEAD OF THE PACK
Fully digital circuits, guaranteeing the highest possible operating reliability under all environmental conditions, support all the control and monitoring operations. If one unit dysfunctions, it does not affect the general system operation.

DIMENSIONS

UPS power
(kVA)
back-up time
at 75 % of load
dimensions WxDxH (mm) weight
(kg)
 Mod-TC 230/245/260 from 3 to 6  > 60 minutes (may be increased to several hours)  600x600x1425  370/380/390
 Mod-TC 360 (N+1 redundant up to  6000VA)  110 minutes (may be increased to several hours)  600x600x1425  610
Mod-TC 390 (N+1 redundant up to  9000VA)  80 minutes (may be increased to several hours)  600x600x1425  614

 

TECHNICAL DATA

Input
Voltage (V) 230V (1ph) +/- 20 % or 400V (3ph + N) +/- 20 %
Frequency  50 or 60 Hz +/- 10 %
Current  sinusoidale absorption
Power Factor > 0.98
Sortie
Voltage(V)  230 V +/- 3 %
(settable for 208/220/240V)
Frequency  50 or 60 Hz +/- 2 %
Automatic by-pass  voltage selected +/- 15 %
frequency selected +/- 2 %
Admissible crest factor 3:1
Efficiency AC/AC 90 % On line – 97 % in ECO MODE
Environment
Operating temperature  from 0 to + 40°C
Sound level (ISO 3746)     < 50 dBA for 3 kVA
< 52 dBA for 4.5-6 kVA
Conformity to standards
Safety / EMC standards
European UPS standard EN 50091 and CE marking
(EN) IEC 62040-1-1 / (EN) IEC 60091-1
Electromagnetic emissions EN 50091-2 (level B) – 1.5 – 3 kVA
EN 50091-2 (level A) – 4.5 – 6 kVA

UNI VISION PRO software
MAIN CHARACTERISTICS

• shutdown command to the PCs/Servers connected in the network
• several operating systems supported
• notification of alarm messages via e-mail
• JNC (Java & .NET™ Shutdown Client) optional.

ADVANTAGES
COMPLETE AND EFFECTIVE PROTECTION

UNI VISION pro provides the system on which it is installed with full management and control of all sensitive UPS operating parameters and of the quality of the electric power supplying the equipment.

NET VISION
SNMP – Web manager
MAIN CHARACTERISTICS

• T-SERVICE, remote diagnostics functions with automatic sending of report and alarms via e-mail to the local authorised Socomec UPS Service Centre
• SNMP /HTTP agent for easy control of remote stations
• JNC (Java&.NET TM Shutdown Client) optional.

ADVANTAGES
EASY CONNECTION TO THE NETWORK

To be able to monitor and interact with the UPS from any PC equipped with an Internet Browser, just make a connection with NET VISION between the UPS and your company´s network. The UPS can then be managed like any other network peripheral.